MBI GmbH | Brigittenstr. 41a | 47608 Geldern

Telefon: 02831 / 9 82 22 | Telefax: 02831 / 44 58 | E-Mail: infombi-verteilerbau.de

Einkammerverteiler

Manifold size Outflow dimension Max. manifold connections* Hot water flow rate Output at Δt=20°C
60 up to DN 32 up to DN 40 up to 3,5 m³/h up to 75 kW
80 up to DN 40 up to DN 50 up to 6 m³/h up to 135 kW
100 up to DN 50 up to DN 65 8,5 - 11 m³/h 190 - 250 kW
120 up to DN 65 up to DN 80 14 - 18 m³/h 320 - 410 kW
160 up to DN 80 up to DN 100 18 - 32 m³/h 410 - 725 kW
200 up to DN 100 up to DN 125 32 - 42 m³/h 725 - 950 kW
250 up to DN 125 up to DN 150 49 - 72 m³/h 1100 - 1650 kW
300 up to DN 150 up to DN 200 72 - 114 m³/h 1650 - 2600 kW
350 up to DN 200 up to DN 250 114 - 138 m³/h 2600 - 3100 kW
400 up to DN 250 up to DN 300 up to 180 m³/h up to 4100 kW
450 up to DN 300 up to DN 350 up to 235 m³/h up to 5300 kW
500 up to DN 350 up to DN 400 up to 260 m³/h up to 5800 kW

*max. manifold connections
for following configurations:
Kombinierter Verteiler - Max. Verteileranschlüsse SO
Kombinierter Verteiler - Max. Verteileranschlüsse SU
Kombinierter Verteiler - Max. Verteileranschlüsse V









A =
mm

(for HV80 up to HV120: A = 160 mm or 220 mm)

H =
mm



















Please select only the top DN column on the request form for threaded sockets DN 15 to DN 50.
When using a flange as a pipe socket, in seamless steel tubes with welding-neck flanges (DIN standard, PN 6, PN 10 or PN 16 from DN 25 to DN 400), please select the columns DN and PN.